Commercial load calculationsJourneymanMasterNEC 2026

Commercial general lighting load (2026 NEC Table 120.42(A))

Short answer

Multiply the floor area by the Table 120.42(A) unit load for the occupancy, such as 1.3 VA/ft² for an office or 1.9 VA/ft² for retail. Add 200 VA per foot of show window and 1,200 VA per sign outlet. In the 2026 NEC the 125% continuous factor is applied when sizing the feeder conductors and OCPD, not inside the load calculation.

Updated Original problems, new numbers every time

Live practice

Practice: commercial lighting load

Each problem uses new numbers, so you practice the method rather than memorizing an answer.

Formula

Lighting load (VA) = Floor area (ft²) × Unit load from Table 120.42(A) (VA/ft²)
Continuous feeder sizing (VA) = Lighting load × 1.25
Show window (VA) = 200 × Length (ft); Sign outlet = 1,200 VA
SymbolMeaningUnit
AreaFloor area from the outside dimensions (120.5(C))ft²
Unit loadVA per ft² for the occupancy, Table 120.42(A)VA/ft²

Worked example

Occupancy type in Table 120.42(A): retail. The building has 15,000 ft² of floor area, measured to the outside of the walls. What is the minimum general lighting load for the feeder calculation?

  1. Look up the unit load for this occupancy (retail) in Table 120.42(A): 1.9 VA/ft².
  2. Lighting load: 15,000 ft² × 1.9 VA/ft² = 28,500 VA. Under 120.5(E), do not add 125% in the load calculation itself.

Answer: 28,500 VA

Commercial lighting load, explained

For buildings other than dwellings, the minimum general lighting load is the floor area times a unit load that depends on how the building is used. Open Table 120.42(A) (Table 220.42(A) in 2023) and find the occupancy: office 1.3 VA/ft², retail 1.9, school 1.5, warehouse 1.2 and so on. The values are the same as in 2023. Older books from before 2020 show higher values such as 3.5 VA/ft² for offices; do not use them.

The 125% factor is where 2026 differs from 2023. The 2023 table had a note saying the unit loads already included the 125% continuous-load factor. The NFPA committee record for 2026 shows that note removed and a new 120.5(E) saying load calculations do not apply 125% for continuous loads. That factor now lives in conductor and OCPD sizing (215.2(A)(1) for feeders). Sources still disagree on how to read this, so check Table 120.42(A) and 120.5(E) in your own 2026 book. If a question tells you to apply 125%, follow the question.

Show windows and signs are added on top of the general lighting. A show window counts 200 VA per linear foot, measured along its base (120.14(G)). Each required sign outlet counts at least 1,200 VA (120.14(F)). Both are usually continuous loads.

For a 3-phase feeder, divide the VA by the line-to-line voltage times 1.732 to get amperes.

How to solve it on the exam

  1. Find the occupancy in Table 120.42(A) and read its unit load.
  2. Multiply by the floor area from the outside dimensions.
  3. Add 200 VA per linear foot of show window and 1,200 VA per sign outlet if the question has them.
  4. For feeder conductor sizing of continuous loads, multiply by 1.25 (215.2(A)(1)), then convert to amperes.

Common mistakes

  • Using 2 or 3 VA/ft² (dwelling values) for a commercial building.
  • Using pre-2020 unit loads, such as 3.5 VA/ft² for offices.
  • Mixing up where the 125% goes. The 2026 NEC removed the table note that said 125% was already included. Check your 2026 book and the question wording; never apply 125% twice.
  • Forgetting the 1,200 VA sign outlet or the 200 VA per foot show window load.
  • Leaving out 1.732 when converting a 3-phase load to amperes.

Exam tips

  • Occupancy notes under the table matter: banks are offices, stores and barber shops are retail, clubs are restaurants.
  • If two choices differ by exactly 25%, the question is testing the continuous-load factor. Read whether it asks for the load or for the feeder ampacity.
Calculator

Commercial lighting load calculator

Result–

    Questions people ask

    What is the lighting load for an office in the 2026 NEC?

    1.3 VA per square foot from Table 120.42(A). Multiply by the floor area.

    Does Table 120.42(A) include the 125% continuous load factor?

    The 2023 table said it did. The 2026 committee record shows that note removed, and the new 120.5(E) leaves the 125% to conductor and OCPD sizing. Check the table and 120.5(E) in your own 2026 book.

    How much load is a show window?

    200 VA per linear foot of show window, measured along its base (120.14(G)).

    What is the minimum load for a sign outlet?

    1,200 VA for each required sign outlet (120.14(F)).

    Sources