In force in Texas since Sep 1, 2026

2026 NEC changes that matter on the Texas exam

Updated

If you studied the 2023 NEC, change this: load calculations now live in Article 120 (was 220); the dwelling feeder and service general load drops from 3 to 2 VA per square foot; the optional method takes the first 8 kVA at 100% (was 10 kVA); and 3 to 5 dryers now take 80%.

Article 220 is now Article 120

Load calculations moved to Chapter 1. Most section numbers kept their ending, so 220.55 is now 120.55, but a few moved. Your tabs and highlights from a 2023 book will point to the wrong article.

Topic2023 NEC2026 NEC
Dwelling general lighting (feeders, services)220.41120.41
Number of dwelling general-purpose circuits220.41 / 210.11(A)120.13
Lighting demand factorsTable 220.45Table 120.45
Small-appliance and laundry circuits (1500 VA)220.52(A), (B)120.52(A), (B)
Fastened-in-place appliances (75% for 4 or more)220.53120.53
DryersTable 220.54Table 120.54
Ranges and cooking appliancesTable 220.55Table 120.55
EV charging equipment220.57120.57
Noncoincident loads (heat or AC)220.60120.6
Feeder and service neutral220.61120.61
Optional method, one-family dwelling220.82120.82
Optional method, existing dwelling220.83120.83
Energy management systemsArticle 750Article 130

Article 310 table numbers (310.16, 310.15(B)(1)(1), 310.15(C)(1), 310.12) did not change.

Dwelling general load: 2 VA per square foot

For dwelling feeders and services, the general lighting and general-use receptacle load is now 2 VA per square foot (120.41) instead of 3. It applies in the standard method and the optional method (120.82(B)). Area is measured from the outside dimensions, leaving out open porches and unfinished spaces not adaptable for future use.

Watch out: to count how many general-purpose circuits the dwelling needs, it is still 3 VA per square foot (the new 120.13). A 2,400 ft² house carries 4,800 VA in the feeder calculation but 7,200 VA when counting circuits.

Optional method: the first 8 kVA at 100%

In the optional method for one dwelling (120.82), the general load is taken at 100% for the first 8 kVA and 40% for the rest. It used to be 10 kVA. EV charging equipment is now added separately at 100% of nameplate (120.82(D)), outside the 40% group. The heating and air-conditioning percentages did not change.

Dryers: 80% for 3 to 5

In Table 120.54, 1 or 2 dryers take 100% and 3 to 5 dryers take 80%. In the 2023 edition it was 100% up to 4 and 85% for 5. From 6 up nothing changed. Each dryer still counts as 5,000 W or its nameplate, whichever is larger. Source: NFPA's corrected Handbook page (March 2026), a single but official source.

EV chargers at nameplate

120.57 takes the EV charging equipment load at its nameplate rating. The 2023 edition used 7,200 W or the nameplate, whichever was larger. One 2026 source still repeats the old rule in one step, so for small chargers check the wording in your own book.

Other changes worth a tab

Not confirmed yet

The 2026 change guides list 240.6(A) (standard ampere ratings), Table 250.122 and 314.16 (box fill) as changed, but we could not find in public sources what changed. Until that is confirmed, check those sections in your own book.

Practice with the new numbers in the calculations.

Questions people ask

Since when does the Texas exam use the 2026 NEC?

Since Sep 1, 2026. TDLR adopted it in 16 TAC §73.100, and the PSI bulletin updated 9/15/2026 lists it as the reference.

Is it still 3 VA per square foot?

For counting a dwelling's general-purpose circuits, yes (120.13). For dwelling feeder and service load calculations it is now 2 VA per square foot (120.41), in both the standard and optional methods.

Where did Article 220 go?

It moved to Chapter 1 as Article 120. Most sections kept their ending (220.55 became 120.55), but not all: noncoincident loads went from 220.60 to 120.6.