Conductors and overcurrentJourneymanMasterNEC 2026

Ampacity correction and adjustment (NEC 310.15)

Short answer

To derate a conductor, take its Table 310.16 ampacity (the 90 °C column for 90 °C wire), multiply by the ambient temperature correction factor from Table 310.15(B)(1)(1) and by the Table 310.15(C)(1) adjustment factor for more than three current-carrying conductors. The result may not exceed the ampacity in the termination column.

Updated Original problems, new numbers every time

Live practice

Practice: ampacity correction and adjustment

Each problem uses new numbers, so you practice the method rather than memorizing an answer.

Formula

Adjusted ampacity (A) = Table ampacity (A) × Temperature correction factor × Adjustment factor
Required table ampacity (A) = Load (A) ÷ (Correction factor × Adjustment factor)
SymbolMeaningUnit
AAllowable ampacity from Table 310.16A
CFAmbient temperature correction factor, Table 310.15(B)(1)(1)
AFAdjustment factor for the number of current-carrying conductors, Table 310.15(C)(1)
nCurrent-carrying conductors in the raceway or cableconductors

Worked example

An EMT raceway holds 5 current-carrying 3/0 AWG copper THHN/THWN-2 conductors and runs through an area where the ambient temperature reaches 115 °F. Starting from the 90 °C column of Table 310.16, what is the ampacity of each conductor after correction and adjustment?

  1. Look up Table 310.16, 90 °C copper column, for 3/0 AWG: 225 A.
  2. Look up the correction factor for 115 °F in the 90 °C column of Table 310.15(B)(1)(1): 0.82.
  3. Look up the adjustment for 5 current-carrying conductors in Table 310.15(C)(1): 80%, or 0.80.
  4. Ampacity after correction and adjustment: 225 × 0.82 × 0.80 = 147.60 A.

Answer: 147.60 A

Ampacity correction and adjustment, explained

Table 310.16 ampacities assume an ambient of 30 °C (86 °F) and no more than three current-carrying conductors together. Hotter air, or more conductors heating each other in one raceway, means the conductor can safely carry less current. Correction handles temperature; adjustment handles bundling.

With 90 °C insulation such as THHN/THWN-2 or XHHW-2, start from the 90 °C column and read the correction factor from the 90 °C column too. That is why 90 °C wire is so common: it has more ampacity to lose before it falls below what the terminals allow.

After derating, compare the result with the ampacity in the termination column (60 °C or 75 °C under 110.14(C)). The conductor's usable ampacity is the smaller of the two. When you size a conductor, check both: the derated 90 °C ampacity must carry the load, and so must the termination column with no derating.

Neutrals that carry only unbalanced current and equipment grounding conductors are not counted as current-carrying. Counting neutrals is its own topic; these problems give you the count.

How to solve it on the exam

  1. Count the current-carrying conductors in the raceway or cable. Three or fewer means no adjustment factor.
  2. Look up the ambient correction factor in the column that matches the insulation (90 °C for THHN), using the °C or °F side of the table.
  3. Look up the adjustment percentage in Table 310.15(C)(1) and change it to a decimal (80% = 0.80).
  4. To find ampacity: multiply the table ampacity by both factors. To find a size: divide the load by both factors, then find the first size in the 90 °C column that is at least that large.
  5. Check the termination column: the conductor must also carry the load at 60 °C or 75 °C with no derating. Use the larger size, or the smaller ampacity.

Common mistakes

  • Derating from the 75 °C column when the insulation is rated 90 °C.
  • Reading the temperature correction factor from the wrong column.
  • Multiplying the load by the factors when sizing, instead of dividing.
  • Forgetting the termination check, so the answer uses more ampacity than a 75 °C lug allows.
  • Applying an adjustment factor to three or fewer current-carrying conductors.

Exam tips

  • Write the three numbers on your notepad before you multiply: table ampacity, CF, AF. Most wrong answers skip one of them.
  • Texas attics and rooftops make temperature questions common. The table has a °F column, so you do not need to convert.
Calculator

Ampacity correction and adjustment calculator

Result–

    Questions people ask

    What is the difference between correction and adjustment factors?

    Correction factors account for ambient temperature above or below 30 °C (86 °F). Adjustment factors account for more than three current-carrying conductors in one raceway or cable.

    Can I derate THHN from the 90 °C column?

    Yes. With 90 °C insulation you may apply correction and adjustment to the 90 °C ampacity, as long as the final result does not exceed the 60 °C or 75 °C termination ampacity.

    Do I apply both factors at the same time?

    Yes. When the ambient is above 30 °C and there are more than three current-carrying conductors, multiply the table ampacity by both factors.

    Does the neutral count as a current-carrying conductor?

    Only sometimes. A neutral that carries only the unbalanced current of a circuit does not count, but a neutral on a 4-wire wye feeder with mostly nonlinear loads does. Equipment grounding conductors never count.

    Sources

    About the tables: The exam is open book. These problems cite the 2026 NEC section and table so you practice finding them in your own book. We never print NEC text or tables.