Practice: ampacity correction and adjustment
Each problem uses new numbers, so you practice the method rather than memorizing an answer.
Pick the answer: sizes and ratings come from your code book.
Worked solution
Formula
| Symbol | Meaning | Unit |
|---|---|---|
| A | Allowable ampacity from Table 310.16 | A |
| CF | Ambient temperature correction factor, Table 310.15(B)(1)(1) | |
| AF | Adjustment factor for the number of current-carrying conductors, Table 310.15(C)(1) | |
| n | Current-carrying conductors in the raceway or cable | conductors |
Worked example
An EMT raceway holds 5 current-carrying 3/0 AWG copper THHN/THWN-2 conductors and runs through an area where the ambient temperature reaches 115 °F. Starting from the 90 °C column of Table 310.16, what is the ampacity of each conductor after correction and adjustment?
- Look up Table 310.16, 90 °C copper column, for 3/0 AWG: 225 A.
- Look up the correction factor for 115 °F in the 90 °C column of Table 310.15(B)(1)(1): 0.82.
- Look up the adjustment for 5 current-carrying conductors in Table 310.15(C)(1): 80%, or 0.80.
- Ampacity after correction and adjustment: 225 × 0.82 × 0.80 = 147.60 A.
Answer: 147.60 A
Ampacity correction and adjustment, explained
Table 310.16 ampacities assume an ambient of 30 °C (86 °F) and no more than three current-carrying conductors together. Hotter air, or more conductors heating each other in one raceway, means the conductor can safely carry less current. Correction handles temperature; adjustment handles bundling.
With 90 °C insulation such as THHN/THWN-2 or XHHW-2, start from the 90 °C column and read the correction factor from the 90 °C column too. That is why 90 °C wire is so common: it has more ampacity to lose before it falls below what the terminals allow.
After derating, compare the result with the ampacity in the termination column (60 °C or 75 °C under 110.14(C)). The conductor's usable ampacity is the smaller of the two. When you size a conductor, check both: the derated 90 °C ampacity must carry the load, and so must the termination column with no derating.
Neutrals that carry only unbalanced current and equipment grounding conductors are not counted as current-carrying. Counting neutrals is its own topic; these problems give you the count.
How to solve it on the exam
- Count the current-carrying conductors in the raceway or cable. Three or fewer means no adjustment factor.
- Look up the ambient correction factor in the column that matches the insulation (90 °C for THHN), using the °C or °F side of the table.
- Look up the adjustment percentage in Table 310.15(C)(1) and change it to a decimal (80% = 0.80).
- To find ampacity: multiply the table ampacity by both factors. To find a size: divide the load by both factors, then find the first size in the 90 °C column that is at least that large.
- Check the termination column: the conductor must also carry the load at 60 °C or 75 °C with no derating. Use the larger size, or the smaller ampacity.
Common mistakes
- Derating from the 75 °C column when the insulation is rated 90 °C.
- Reading the temperature correction factor from the wrong column.
- Multiplying the load by the factors when sizing, instead of dividing.
- Forgetting the termination check, so the answer uses more ampacity than a 75 °C lug allows.
- Applying an adjustment factor to three or fewer current-carrying conductors.
Exam tips
- Write the three numbers on your notepad before you multiply: table ampacity, CF, AF. Most wrong answers skip one of them.
- Texas attics and rooftops make temperature questions common. The table has a °F column, so you do not need to convert.
Ampacity correction and adjustment calculator
Questions people ask
What is the difference between correction and adjustment factors?
Correction factors account for ambient temperature above or below 30 °C (86 °F). Adjustment factors account for more than three current-carrying conductors in one raceway or cable.
Can I derate THHN from the 90 °C column?
Yes. With 90 °C insulation you may apply correction and adjustment to the 90 °C ampacity, as long as the final result does not exceed the 60 °C or 75 °C termination ampacity.
Do I apply both factors at the same time?
Yes. When the ambient is above 30 °C and there are more than three current-carrying conductors, multiply the table ampacity by both factors.
Does the neutral count as a current-carrying conductor?
Only sometimes. A neutral that carries only the unbalanced current of a circuit does not count, but a neutral on a 4-wire wye feeder with mostly nonlinear loads does. Equipment grounding conductors never count.
Sources
About the tables: The exam is open book. These problems cite the 2026 NEC section and table so you practice finding them in your own book. We never print NEC text or tables.